Notifier Onyx Fire Alarm Panel

Product code:

    Price: Contact

     

     

Buy now

Hotline: (84) 28 3512 8169

Addressable Fire Alarm Panel NFS-320E NFS-640E NFS2-3030
Signalling Line Circuit 1 SLC  1 SLC,expandable to 2 Up to 10 SLC.
Maximum number of intelligent points Up to 318 Intelligent points (159 detector & 159 module) Up to 636 Intelligent points (159 detector & 159 module per SLC) Up to 3180 Intelligent points (159 detector & 159 module per SLC)
Audio Evacuation FirstCommand  Optional Intergrated Digital Voice Command (DVC) Optional Intergrated Digital Voice Command (DVC)
Program software zones 99 ( plus 16 special programming zones ) 99 ( plus 16 special programming zones ) 2000 ( plus 22 special programming zones )
Logic equations 20 20 1000
Releasing zone  10 10 10
Event history capacity/ Alarm-only 800/200 800/200 4000/1000
Character LCD display QWERTY keypad 80 80/640 640
Approved  UL/FM
Feature - Portfolio includes Addr / Conventional Panels & Gas releasing Panels / Detectors & Modules.
- Graphical User Interface
- Bacnet / Modbus for BMS / SCADA
- Faster polling and response time : Permits the largest number of devices per loop in the industry;  Response times exceed worldwide code requirements(<5 sec ).
Certificate of Origin  USA (Panels) /  China & India – detectors and Modules
Notifer-net  Supports up to 200+ Node Addresses on HS-NCM or  103 nodes on NCM or up to 53 node when it is set up to circulate live paging from a DVC node
Network communication speeds 12Mb for wire , 100Mb for multi-mode , single-mode fiber.
Detection Technology Smoke/ Heat/ Multi-Sensor, Multicolor LEDs provide feedback, Manual sensitivity adjustment — nine levels.
Setting Addressable  All  the  Onyx  intelligent  peripherals  are hard addressing, Rotary, decimal addressing.