Linear Heat Detector Comparison Chart
|
|
Feature
|
Protectowire Digital
|
Analog Integrating (1)
|
Continuous
Thermocouple (1)
|
|
Maximum Zone Length
|
Up to 5,000 FT. (1,524 m)
|
1,500 FT. (457.2m)
|
2,000 FT. (609.6m)
|
|
Alarm Point Location
|
YES
|
NO
|
NO
|
|
Multiple Alarm Points Within Zone
|
YES
|
NO
|
NO
|
|
Underwriters Laboratory (UL) Listed
|
YES
|
NO
|
NO
|
|
Factory Mutual (FM) Approved
|
YES
|
YES
|
NO
|
|
Alarm Point Setting Unaffected by Changes in Ambient Temperature
|
YES
|
NO
|
YES
|
|
Compatible with Standard Initiating Devices (Manual Stations, Contact Devices and Smoke Detectors)
|
YES
|
NO
|
NO
|
|
Pre-Alarm Capability
|
YES
|
YES
|
YES
|
|
Approved for use in Hazardous Locations
|
YES
|
YES
|
? *
|
|
Easy to Splice / Terminate
|
YES
|
NO
|
? *
|
|
Maximum Alarm Temperature
|
356°F (180°C)
|
500°F (260°C)
|
350°F (177°C)
|
|
Expected Service Life
|
Current Installations Greater than 20 Years
|
? *
|
? *
|
|
Requires On Site Calibration
|
NO
|
YES
|
NO
|
|
Size
|
5/32 in. (4 mm)
|
0.09 in. (2.28 mm)
|
1/8 in. (3.175 mm)
|
|
Annual Maintenance per NFPA 72, 1999
|
Minimal
|
Heat Test - Must alarm within 1 minute
|
? *
|
|
Accuracy dependent on length
|
NO
|
YES
|
NO
|
|
Designed and Manufactured by and ISO-9001 Registered Company
|
YES
|
? *
|
? *
|
|
Feature
|
Protectowire Digital
|
Analog Integrating (1)
|
Continuous
Thermocouple (1)
|
(1) - Based on available information at the time of publication 4/13/01
? * - Information unknown or not available
|